15.5kV Ferrule Mount Transformer Fuses
Mersen fuses for the protection of transformers and distribution lines deliver overload and short circuit protection. These current-limiting fuses will melt at current that can be as low as 1.7 times the fuse current ratings up to its maximum interrupting rating. These fuses are designed to withstand the transformer magnetizing inrush current. They have 2" (size C), 3" (size D) and 2x3" (size DD) inch diameter barrels with ferrules and are mounted in spring reinforced clips.
Mersen fuses for the protection of transformers and distribution lines deliver overload and short circuit protection. These current-limiting fuses will melt at current that can be as low as 1.7 times the fuse current ratings up to its maximum interrupting rating. These fuses are designed to withstand the transformer magnetizing inrush current. They have 2" (size C), 3" (size D) and 2x3" (size DD) inch diameter barrels with ferrules and are mounted in spring reinforced clips.
Product data sheets
- DS-15.5kV-Ferrule-Mount-Transformer-Protection-Mersen
pdf - 429.74 KB
Product Applications
Compliance
- COM-RoHS-RS000083-15.5kV-Ferrule-Mount-Transformer-Fuses-Mersen
pdf - 142.18 KB
- COM-REACH-RE000083-15.5kV-Ferrule-Mount-Transformer-Fuses-Mersen
pdf - 147.37 KB
- COM-REACH-RE000083-15.5kV-Ferrule-Mount-Transformer-Fuses-Mersen
pdf - 147.37 KB
Key features & benefits
Amp-Trap CS-3 and 9F62 series are UL listed for compatibility with UL listed equipment
Ferrule mounting for standard clips and interchangeability with other brands of fuses
Current-limiting for superior equipment protection
Non-venting for silent operation
Metal embossed catalog number and manufacturing date for lasting identification
Outdoor usage for the 9F62 and 9F60 type EJO
Blown-fuse indicator to give positive identification of open fuse: Amp-Trap: 2" Barrel 1 lb tripped force - 0.19 Inch; Amp-Trap: 3" Barrel 2 lb tripped force - 0.50 Inch; 9F60/9F62: 0.125 lb tripped force – 0.20 Inch
Applications
Protection for 12 kV to 15.5 kV transformers or distribution systems.
Frequency (Hz) | 50/60 Hz |
Amperage Range | 2 to 200 A |
Speed/Characteristic | E-Rated |
Reach Compliant | Yes |
Max Operating Temp. | 80 °C |
Max Storage Temp. | 80 °C |
Min Storage Temp. | -25 °C |
Harmonized System | 853510 |
Reference Finder
Scroll
Item number | Ampere rating | Fuse size | Clearing I2t At Rated Voltage | Indication System | Product weight |
---|---|---|---|---|---|
9F60CJH002 See product
|
2A | - | - | Yes | 1.5876kg |
9F60CJH003 See product
|
3A | - | - | Yes | 1.5876kg |
9F60CJH005 See product
|
5A | - | - | Yes | 1.5876kg |
9F60CJH007 See product
|
7A | - | - | Yes | 1.5876kg |
9F60CJH010 See product
|
10A | - | - | Yes | 1.5876kg |
9F60DMH001 See product
|
1A | - | - | Yes | 1.9278kg |
9F60DMH002 See product
|
2A | - | - | Yes | 1.9278kg |
9F60DMH003 See product
|
3A | - | - | Yes | 1.9278kg |
9F60DMH005 See product
|
5A | - | - | Yes | 1.9278kg |
9F60DMH007 See product
|
7A | - | - | Yes | 1.9278kg |