9F59UBE201
Series: 23.0kV ETP Fuses
ETP 23000V 12K / 8T Configuration: 201
The Sure Guard ETP back-up current-limiting fuses are designed to protect overhead distribution systems and are used in series with another protective device (such as an expulsion fuse). This combination limits the high-fault current to a safe level, thus providing protection through the complete range. As its name implies, the “ETP” is for External Transformer Protection. For conventional transformers protected by expulsion-fuses cutouts, the ETP can be installed in series with the cutout. For self protected transformers, the ETP can be applied on the high-voltage bushing in series with the internal transformer expulsion fuse.
ETP 23000V 12K / 8T Configuration: 201
The Sure Guard ETP back-up current-limiting fuses are designed to protect overhead distribution systems and are used in series with another protective device (such as an expulsion fuse). This combination limits the high-fault current to a safe level, thus providing protection through the complete range. As its name implies, the “ETP” is for External Transformer Protection. For conventional transformers protected by expulsion-fuses cutouts, the ETP can be installed in series with the cutout. For self protected transformers, the ETP can be applied on the high-voltage bushing in series with the internal transformer expulsion fuse.
Datasheets
pdf - 811.57 KB
Item number | 9F59UBE201 |
Description | ETP 23000V 12K / 8T Configuration: 201 |
EAN/UPC Code | 782001401771 |
Rated voltage AC UL | 23000 V |
AC or DC | AC |
AC Max I.R./Breaking Capacity: I1 | 50 kA |
Design Details | 201 |
Connection/Terminal Material | Brass |
Product Diameter | 55.6 mm |
Product Length | 487.2 mm |
Sell Pack Quantity | 1 EA |
Sell Pack Weight | 2.7311 kg |
Sell Pack Width | 57.2 mm |
Sell Pack Length | 60.5 mm |
Sell Pack Height | 593.9 mm |
Product group | Medium Voltage IEEE Fuses |
Body/Insulating Material | Epoxy |
Product Weight | 2.6009 kg |