Fused Coordination Panelboard
-
Mersen’s Fused Coordination Panelboard is designed to meet requirements defined by the National Electrical Code (NEC) to protect critical power operations.
These panels are provided with a default short circuit current rating (SCCR) of 200kA and provide overcurrent protection through a combination of a circuit breaker and fuse. The circuit breaker is designed to be resettable on operations for overloads and operate the series fuse for faults up to 200kA. Mersen’s Fused Coordination Panelboard can simplify the process in achieving code compliance for designers.
The Product Configuration and Selection Tool allows Mersen partners to design their own custom-configured panelboard by selecting the ratings, features, and options you want via a graphical interface or selection of features. The Configuration tool will also provide a detailed quote and in of the job in PDF format. Mersen specialists can also work with you to design a solution that fits your requirements.
-
Benefits
Mersen’s Fused Coordination Panelboard (MFCP) does not require fuse replacement on common overload conditions and branch circuits can simply be reset. Mersen’s Amp-Trap 2000® class CC and class J fuses ensure minimal fuse let-thru energies and makes it easy to provide system coordination with our easy 2:1 coordination ratios for short circuits.
Mersen’s fused selective coordination panelboard is a UL67 listed panelboard that utilizes our commonly available class CC and J fuses.
- Circuit Breaker trips instead of Fuse opening with 2X rating
- Mersen Panel is UL listed to accept any manufacturer’s Class CC and J fuse
- Class CC and J fuses are commonly stocked
- Load Connections UL Listed for 2 wires to help with Inspection during last-minute changes
-
Capabilities
RATINGS:
Volts:
- 120/208V, 3Ø, 4-wire;
- 120/240V, 1Ø, 3-wire;
- 277/480V, 3Ø, 4-wire;
- 347/600V, 3Ø, 4-wire
Amps: Main Bus Ampacity ranges from 250A to 400A
Number of Circuits: Up to 2 circuits
SCCR: 200kA@600V
APPROVALS:
UL 67 Listed Panelboard
UL 50 Listed Enclosure
Meets NEC® selective coordination code requirements for the following power systems:
- 700.8 (Emergency)
- 700.27 (Legally Required Standby)
- 708.54 (Critical Operations)
-
Design Guide
Branch Circuit Protection:
- UL Fuse/Circuit Breaker combination
- Resettable overload protection
- True class J and CC protection
Only Three Branch Fuse Sizes:
- 15A to 30A → ATDR30
- 35A to 60A → AJT60
- 70A to 100A → AJT100
Width:
- 20" wide
Main Options:
- Main Lug Only (MLO)
- Main non-fused switch
- Main non-fused switch with fuses
- Up to 42 Branch Circuits per Panel
Main Bus:
- Standard silver-plated copper, with optional tin-plated aluminum
Enclosures:
- NEMA 1, 12, 3R
Optional Features:
- UL 1449 Listed surge protection devices (required per NEC 700.8)
- Blown fuse indication (30A, 60A)
-
Resources
Brochures and Flyers
11/28/2024
Fused Coordination Panelboards Brochurepdf - 3.74 MB
Brochures and Flyers
11/28/2024
Fused Coordination Panelboard FAQs Brochurepdf - 3.3 MB