P1023145 - M01A0E11G
NH fuse-switch disconnector MULTIVERT® Size 00 160A 3x1-Pole switching Bus bar system 185mm Clamp Strap Al/Cu clamps FM ready
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 160A 185 mm single pole switching are for installation on to 185 mm bus bar systems. MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
NH fuse-switch disconnector MULTIVERT® Size 00 160A 3x1-Pole switching Bus bar system 185mm Clamp Strap Al/Cu clamps FM ready
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 160A 185 mm single pole switching are for installation on to 185 mm bus bar systems. MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
Datasheets
Compliances
pdf - 212.72 KB
pdf - 224.71 KB
Item number | P1023145 |
Catalogue No | M01A0E11G |
Description | NH fuse-switch disconnector MULTIVERT® Size 00 160A 3x1-Pole switching Bus bar system 185mm Clamp Strap Al/Cu clamps FM ready |
EAN/UPC Code | 9008567002933 |
Frequency (Hz) | 50 ... 60 Hz |
Rated voltage AC IEC | 690 V |
Ampere Rating | 160 A |
Utilization Category | AC 22 B @ Ue = AC 400 V; Ie = 160 A AC 20 B @ Ue = AC 690 V; Ie = 160 A |
Switchability | coupure 3x1-pôle |
ROHS Compliant | Yes |
AC or DC | AC |
Short Circuit Current Rating (SCCR) | 80kA@Ue = AC 500 V; Ie = 160 A |
Fuse Size | 00 |
Design Details | MULTIVERT® M01A0G with cabling of instrument leads |
Number of Poles | 3-Pole |
Degree of Pollution | 3 |
Rated Impulse Withstand Voltage | 4 kV |
Rated Insulation Voltage | 1000 V |
Rated SC Withstand | 4.2 kA / 1 s |
Max Power dissipation of Fuse Links Pn | 12 W |
Max Power dissipation of Solid Links Pn | 1.2 W |
Power Dissipation by Ith without Fuse-Links | 22 W |
Power Dissipation by Ith without Solid Links | 34 W |
Rated short circuit making capacity with solid links Icm | 6.3 kA |
Installation Mounting | Bus bar system 185 mm |
Product Width | 50 mm |
Product Length | 120 mm |
Product Height | 664 mm |
Sell Pack Quantity | 1 EA |
Sell Pack Weight | 2.25 kg |
Sell Pack Width | 125 mm |
Sell Pack Length | 673 mm |
Sell Pack Height | 51 mm |
Product group | IEC Fuse Switch Disconnectors |
Product Weight | 2.25 kg |
Conventional Free Air thermal Current With Fuse-Links Ith | 160 A |
Conventional Free Air thermal Current - Solid Links | 200 A |