L1023165 - 1.100.062
Series: MULTIVERT® 250A , Size 1, 690VAC
NH fuse-switch disconnector MULTIVERT® Size 1 250A 3x1-Pole switching Bus bar system 185mm Screw M10 ct1P c.
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 250A are for installation on to 185mm bus bar systems. MULTIVERT® 250A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 1: 250A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
NH fuse-switch disconnector MULTIVERT® Size 1 250A 3x1-Pole switching Bus bar system 185mm Screw M10 ct1P c.
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 250A are for installation on to 185mm bus bar systems. MULTIVERT® 250A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 1: 250A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
Datasheets
Compliances
pdf - 326.58 KB
pdf - 212.52 KB
Item number | L1023165 |
Catalogue No | 1.100.062 |
Description | NH fuse-switch disconnector MULTIVERT® Size 1 250A 3x1-Pole switching Bus bar system 185mm Screw M10 ct1P c. |
EAN/UPC Code | 9008567008225 |
Frequency (Hz) | 50 ... 60 Hz |
Rated voltage AC IEC | 690 V |
Ampere Rating | 250 A |
Utilization Category | AC 23 B @ Ue = AC 400 V; Ie = 250 A AC 23 B @ Ue = AC 500 V; Ie = 250 A AC 22 B @ Ue = AC 690 V; Ie = 250 A |
Switchability | coupure 3x1-pôle |
ROHS Compliant | Yes |
AC or DC | AC |
Short Circuit Current Rating (SCCR) | 120kA@Ue = AC 400 V; Ie = 250 A / 120kA@Ue = AC 500 V; Ie = 250 A / 120kA@Ue = AC 690 V; Ie = 250 A |
Fuse Size | 1 |
Design Details | MULTIVERT® 1.100.000 with integrated C.T. 250/5A, 3,75 VA, class 0,5; calibrated, for single pole measurement (ready fitted in pole 1) |
Number of Poles | 3-Pole |
Degree of Pollution | 3 |
Rated Impulse Withstand Voltage | 12 kV |
Rated Insulation Voltage | 1000 V |
Rated SC Withstand | 8 kA / 1 s |
Max Power dissipation of Fuse Links Pn | 23 W |
Max Power dissipation of Solid Links Pn | 2.6 W |
Power Dissipation by Ith without Fuse-Links | 35 W |
Power Dissipation by Ith without Solid Links | 90 W |
Rated short circuit making capacity with solid links Icm | 16 kA |
Installation Mounting | Bus bar system 185 mm |
Product Width | 98 mm |
Product Length | 190 mm |
Product Height | 685 mm |
Sell Pack Quantity | 1 EA |
Sell Pack Weight | 4.6 kg |
Sell Pack Width | 100 mm |
Sell Pack Length | 688 mm |
Sell Pack Height | 195 mm |
Product group | IEC Fuse Switch Disconnectors |
Product Weight | 4.6 kg |
Conventional Free Air thermal Current With Fuse-Links Ith | 250 A |
Conventional Free Air thermal Current - Solid Links | 400 A |