M1200L12
Series: UL98 Fused Switch
UL 98 Fusible Switch 600VAC Class L 1200A 3-Pole Configuration: 1-2
Mersen’s fusible disconnect switches are listed to UL 98 and bear the CE mark conforming to IEC 60947-3. They are “service entrance” devices capable of fully rated load-break and load-make. While longterm safety, reliability, and functionality are always paramount in the design of our products, these switches are also engineered to have the smallest footprint. The modular design allows placement of the handle anywhere amongst the poles. The fuse doors cannot open when the switch is in the “ON” position, and all switches are double-break, which isolates both fuse clips from voltage during fuse replacement. The switches’ “Test” position allows actuation of the auxiliary contacts without main power. Power taps enable energizing a CPT or surge device without the need for a separate terminal block. A wide range of ergonomic handles and accessories is available.
UL 98 Fusible Switch 600VAC Class L 1200A 3-Pole Configuration: 1-2
Mersen’s fusible disconnect switches are listed to UL 98 and bear the CE mark conforming to IEC 60947-3. They are “service entrance” devices capable of fully rated load-break and load-make. While longterm safety, reliability, and functionality are always paramount in the design of our products, these switches are also engineered to have the smallest footprint. The modular design allows placement of the handle anywhere amongst the poles. The fuse doors cannot open when the switch is in the “ON” position, and all switches are double-break, which isolates both fuse clips from voltage during fuse replacement. The switches’ “Test” position allows actuation of the auxiliary contacts without main power. Power taps enable energizing a CPT or surge device without the need for a separate terminal block. A wide range of ergonomic handles and accessories is available.
Datasheets
pdf - 1.18 MB
Item number | M1200L12 |
Description | UL 98 Fusible Switch 600VAC Class L 1200A 3-Pole Configuration: 1-2 |
EAN/UPC Code | 782001462574 |
Rated voltage AC UL | 600 V |
Rated voltage DC UL | 250 V |
Ampere Rating | 1200 A |
ROHS Compliant | Yes |
AC or DC | AC/DC |
Short Circuit Current Rating (SCCR) | 200 kA |
Fuse Type/Class | Class L |
Short Circuit Rating (Standalone) | 200 kA |
Number of Poles | 3-Pole |
Connection/Terminal Material | Silver-Plated Copper |
Connection/Terminal Type | Blade |
Max Fuse Rating | 1200 A |
Max Horsepower Rating/FLA | 3-Phase: 240V 250HP, 480V 500HP, 600V 500HP |
Contact Type | Intervalo Duplo |
Rated Insulation Voltage | 1000 V |
Installation Mounting | Direct Screw Mount |
Product Width | 429 mm |
Product Length | 426 mm |
Product Height | 293.9 mm |
Sell Pack Quantity | 1 EA |
Sell Pack Weight | 47.1509 kg |
Sell Pack Width | 439.9 mm |
Sell Pack Length | 564.9 mm |
Sell Pack Height | 700 mm |
Product group | UL/CSA Switches |
Product Weight | 44.9056 kg |