Back
Where to buy Contact us
PHP-Limitor®PTS-MSL

Limitor® - PTS Back-up Fuses, with Low Power Dissipation and Thermal Striker

Approvals & Standards
IEC 60282-1
VDE 0670 part 4
VDE 0670 part 402
DIN 43625

Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades. For the Limitor®-PTS range, Mersen innovates with new fuse-element designs to reduce power losses and new thermal striker to prevent overheating in the fuse compartment of the switch gear. Mersen uses the best materials : fuse-elements are in pure silver, caps are in copper coated with silver and body is in ceramic. Limitor®-PTS HV fuse-links are dedicated to protect transformers in combination with air or gas insulated switchgear against the thermal and dynamic effects of short-circuits. Siemens and Ormazabal recommend Limitor®-PTS HV fuses to be used in their gas-insulated switchgear.

Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades. For the Limitor®-PTS range, Mersen innovates with new fuse-element designs to reduce power losses and new thermal striker to prevent overheating in the fuse compartment of the switch gear. Mersen uses the best materials : fuse-elements are in pure silver, caps are in copper coated with silver and body is in ceramic. Limitor®-PTS HV fuse-links are dedicated to protect transformers in combination with air or gas insulated switchgear against the thermal and dynamic effects of short-circuits. Siemens and Ormazabal recommend Limitor®-PTS HV fuses to be used in their gas-insulated switchgear.

Key features & benefits

  • Low switching voltage

  • Large current ratings range

  • Very low power losses

  • Energy efficency

  • New thermal striker patented by Mersen to prevent overheating

  • Medium striker 80N / 30mm

  • New cap design for a better compatibility with all types of clips and easier assembly

  • Outdoor and indoor use

  • Coordination with IEC 60787, IEC 62271-105 and VDE 0670 T303

Applications

  • Best used in SF6 insulated switch gear and compact switch gear

  • HV Transformer protection

Technical Specifications
Voltage Range 6 ... 36 kV
Amperage Range 10 ... 160 A
Reach Compliant Yes

Reference Finder

Item number Ampere rating Fuse size Clearing I2t At Rated Voltage Indication System Product weight
R1018317 - 45DB120V100PTS3 See product
100A d=78mm, L=442mm 150kA²s Yes 5.1kg
R1032945 - 45DB120V10PTS2 See product
10A d=56mm, L=292mm 3000A²s Yes 1.6kg
S1018318 - 45DB120V125PTS3 See product
125A d=78mm, L=442mm 300kA²s Yes 5.1kg
S1032946 - 45DB120V16PTS2 See product
16A d=56mm, L=292mm 3700A²s Yes 1.6kg
T1032947 - 45DB120V20PTS2 See product
20A d=56mm, L=292mm 4700A²s Yes 1.6kg
V1018320 - 45DB120V160PTS3 See product
160A d=78mm, L=442mm 500kA²s Yes 5.1kg
V1032948 - 45DB120V25PTS2 See product
25A d=56mm, L=292mm 4920A²s Yes 1.6kg
W1032949 - 45DB120V32PTS2 See product
31.5A d=56mm, L=292mm 7000A²s Yes 1.6kg
X1018322 - 45DB240V50PTS See product
50A d=65mm, L=442mm 39kA²s Yes 3.3kg
X1032950 - 45DB120V40PTS2 See product
40A d=56mm, L=292mm 14kA²s Yes 1.6kg
Back to top