P1003894 - BJU42V080PA
British Standard fuse-link IEC BS88 gG Type 110x36 415VAC 80A
The majority of existing street lighting networks are normally protected by a common Feeder Protection Device (FPD). FDP is based on a simple overcurrent unidirectional technique to protect against faults on the street lighting cables. The Mersen fuse technology ensures safety in street lighting applications by providing better coordination, immediate isolation and ensures fire safety through safe and correct fuse selection.
British Standard fuse-link IEC BS88 gG Type 110x36 415VAC 80A
The majority of existing street lighting networks are normally protected by a common Feeder Protection Device (FPD). FDP is based on a simple overcurrent unidirectional technique to protect against faults on the street lighting cables. The Mersen fuse technology ensures safety in street lighting applications by providing better coordination, immediate isolation and ensures fire safety through safe and correct fuse selection.
Datasheets
pdf - 386.48 KB
Technical Specifications
Item number | P1003894 |
Catalogue No | BJU42V080PA |
Description | British Standard fuse-link IEC BS88 gG Type 110x36 415VAC 80A |
EAN/UPC Code | 3605340479157 |
Rated voltage AC IEC | 415 V |
Ampere Rating | 80 A |
ROHS Compliant | Yes |
AC or DC | AC |
Speed/Characteristic | gG |
Fuse Size | 110x36 |
Mounting | Clip |
Clearing I2t At Rated Voltage | 21000 A²s |
Melting I2t | 4150 A²s |
AC Max I.R./Breaking Capacity: I1 | 80 kA |
Connection/Terminal Material | Copper |
Connection/Terminal Type | Blade |
Product Diameter | 36.1 mm |
Product Length | 110 mm |
Product Height | 31 mm |
Sell Pack Quantity | 6 EA |
Sell Pack Weight | 1.112 kg |
Sell Pack Width | 235 mm |
Sell Pack Length | 120 mm |
Sell Pack Height | 40 mm |
Product group | Low Voltage IEC Fuses |
Body/Insulating Material | Ceramic |
Product Weight | 0.185 kg |
Power Dissipation at Rated Current Value | 8.4 W |