D1023158 - 1.003.308
NH fuse-switch disconnector MULTIVERT® Size 00 160A 1x3-Pole switching Bus bar system 60mm Clamp Strap / Screw top terminal FM ready
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 160A 60mm triple pole switching are for installation on to 60 mm bus bar systems. MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
NH fuse-switch disconnector MULTIVERT® Size 00 160A 1x3-Pole switching Bus bar system 60mm Clamp Strap / Screw top terminal FM ready
MULTIVERT® NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors. They are designed for installation on to bus bars in triple pole arrangements. MULTIVERT® 160A 60mm triple pole switching are for installation on to 60 mm bus bar systems. MULTIVERT® 160A are designed for NH fuse-links in accordance with IEC/EN 60269-2, VDE 0636-2, size 00: 160A. The system is a modular system, that allows the installation of individual components. MULTIVERT® offer the user the possibility of fast and easy installation as well as a high degree of protection during installation and maintenance.
Datasheets
Compliances
Item number | D1023158 |
Catalogue No | 1.003.308 |
Description | NH fuse-switch disconnector MULTIVERT® Size 00 160A 1x3-Pole switching Bus bar system 60mm Clamp Strap / Screw top terminal FM ready |
EAN/UPC Code | 9008567007990 |
Frequency (Hz) | 50 ... 60 Hz |
Rated voltage AC IEC | 690 V |
Ampere Rating | 160 A |
Utilization Category | AC 23 B @ Ue = AC 400 V; Ie = 160 A AC 22 B @ Ue = AC 500 V; Ie = 160 A AC 22 B @ Ue = AC 690 V; Ie = 100 A DC 21 B @ Ue = DC 220 V; Ie = 160 A DC 21 B @ Ue = DC 440 V; Ie = 100 A |
Switchability | coupure 1x3-pôle |
ROHS Compliant | Yes |
AC or DC | AC |
Short Circuit Current Rating (SCCR) | 120kA@Ue = AC 400 V; Ie = 160 A / 120kA@Ue = AC 500 V; Ie = 160 A / 50kA@Ue = AC 690 V; Ie = 100 A |
Fuse Size | 00 |
Design Details | Clamp Strap / Screw top terminal |
Number of Poles | 3-Pole |
Degree of Pollution | 3 |
Rated Impulse Withstand Voltage | 8 kV |
Rated Insulation Voltage | 1000 V |
Rated SC Withstand | 4.5 kA / 1 s |
Max Power dissipation of Fuse Links Pn | 12 W |
Max Power dissipation of Solid Links Pn | 1.2 W |
Power Dissipation by Ith without Fuse-Links | 18 W |
Power Dissipation by Ith without Solid Links | 44 W |
Rated short circuit making capacity with solid links Icm | 4.5 kA |
Installation Mounting | Bus bar system 60 mm |
Product Width | 50 mm |
Product Length | 116 mm |
Product Height | 406 mm |
Sell Pack Quantity | 1 EA |
Sell Pack Weight | 1.5 kg |
Sell Pack Width | 130 mm |
Sell Pack Length | 440 mm |
Sell Pack Height | 51 mm |
Product group | IEC Fuse Switch Disconnectors |
Product Weight | 1.5 kg |
Conventional Free Air thermal Current With Fuse-Links Ith | 160 A |
Conventional Free Air thermal Current - Solid Links | 250 A |