NH fuse-links aM 500VAC , double indicator/live gripping-lugs size 000, 00, 0, 1, 2, 3
The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.
Type "aM" NH fuse-links are partial-range breaking capacity fuse-links, used to protect motor circuits as they are strongly current-limiting and have low power losses. They interrupt currents from 6.3 times In up to their maximum breaking capacity and are therefore suited for short-circuit protection only. They must be associated with other switchgear for protection against overloads. These fuse-links can have a rated current equal to the motor's nominal current.
The NH system is classified among plug-in fuse systems and is composed of: * fuse-base (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional.
Type "aM" NH fuse-links are partial-range breaking capacity fuse-links, used to protect motor circuits as they are strongly current-limiting and have low power losses. They interrupt currents from 6.3 times In up to their maximum breaking capacity and are therefore suited for short-circuit protection only. They must be associated with other switchgear for protection against overloads. These fuse-links can have a rated current equal to the motor's nominal current.
Product data sheets
Brochures and Flyers
- DS-Microswitches-for-NH-fuse-links-size-000-to-3-EN
pdf - 264.6 KB
- DS-NH-Fuse-Handles-EN
pdf - 804.83 KB
- BR-Panel-Builder-Mersen-EN
pdf - 6.01 MB
Compliance
- COM-BV-certificate-3924-NH-AM-GG-indicator-fuses
pdf - 575 KB
- COM-LR-certificate-NH-fuses
pdf - 5.47 MB
- COM-REACH-declaration-0018-NHAM-500V-690V-fuses
pdf - 245.16 KB
- COM-CE-ROHS-declaration-0018-NHAM-500V-690V-fuses
pdf - 130.82 KB
- COM-UKCA-declaration-0018-NHAM-500V-690V-fuses
pdf - 166.36 KB
Key features & benefits
Dimensions according to DIN 43 620 parts 1 to 4
Non-isolated gripping lugs
Double indicator
0% cadmium
Applications
aM: Partial purpose, motor circuit protection
Amperage Range | 2 ... 630 A |
Speed/Characteristic | aM |
CE Conformity | Yes |
Reach Compliant | Yes |
Reference Finder
Scroll
Item number | Ampere rating | Fuse size | Clearing I2t At Rated Voltage | Indication System | Product weight |
---|---|---|---|---|---|
T232501 - NH000AM50V35 See product
|
35A | NH000 | - | Yes | 0.13kg |
T232524 - NH3AM50V450 See product
|
450A | NH3 | - | Yes | 1.05kg |
V232502 - NH000AM50V40 See product
|
40A | NH000 | - | Yes | 0.13kg |
V232525 - NH3AM50V500 See product
|
500A | NH3 | - | Yes | 1.05kg |
W232503 - NH000AM50V50 See product
|
50A | NH000 | - | Yes | 0.13kg |
X232504 - NH000AM50V63 See product
|
63A | NH000 | - | Yes | 0.13kg |
Y232505 - NH00AM50V100 See product
|
100A | NH00 | - | Yes | 0.2kg |
Z232506 - NH00AM50V125 See product
|
125A | NH00 | - | Yes | 0.2kg |