NH fuse-links gTr 400VAC, middle indicator/live gripping-lugs size 2, 3, 4a
The NH system is classified among plug-in fuse systems and is composed of: * fuse-base, (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional.
NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.
The NH system is classified among plug-in fuse systems and is composed of: * fuse-base, (possibly including terminal covers and phase barriers) * fuse-link with blade contact * fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional.
NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.
Product data sheets
- DS-NH-fuse-links-gTr-400VAC-middle-indicator-EN
pdf - 617.37 KB
Brochures and Flyers
- DS-NH-Fuse-Handles-EN
pdf - 804.83 KB
Compliance
- COM-REACH-declaration-0019-NHGTR-400V-fuses
pdf - 244.94 KB
- COM-CE-ROHS-declaration-0019-NHGTR-400V-fuses
pdf - 130.75 KB
- COM-UKCA-declaration-0019-NHGTR-400V-fuses
pdf - 166.27 KB
Key features & benefits
Maximum transformer capacity (up to 1,3 x In)
Reduction of unnecessary interruption of operation
Precise cut off of overload
Characteristic adapted to the transformer
Resistant to ageing
Selectivity to fuse links gG
High current limiting
High breaking capacity
Easy selection between transformer and fuse link
Applications
Protection of transformers
Amperage Range | 72 ... 1443 A |
Speed/Characteristic | gTr |
CE Conformity | Yes |
Reach Compliant | Yes |
Reference Finder
Scroll
Item number | Ampere rating | Fuse size | Clearing I2t At Rated Voltage | Indication System | Product weight |
---|---|---|---|---|---|
Y1028719 - NH4AGTR125KVA See product
|
180A | NH4a | - | Yes | 2.2kg |
Y1030513A - NH32GTR315KVA See product
|
455A | NH3 | - | Yes | 1kg |
Z1028720 - NH4AGTR160KVA See product
|
231A | NH4a | - | Yes | 2.2kg |
Z1030514A - NH32GTR400KVA See product
|
577A | NH3 | - | Yes | 1kg |