Back
Where to buy Contact us
PHP-BSOTgG6-MSL

Offset Tag fuse-links gG 690VAC/460VDC

Approvals & Standards
EN 60269-2 section II

The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.

The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.

Key features & benefits

  • Excellent current limitation for all overloads

Applications

  • These fuses are designed for : “General purpose use” protection (gG type)

Technical Specifications
Voltage Range 690VAC/460VDC
Amperage Range 2 ... 800 A
Speed/Characteristic gG
CE Conformity Yes
Reach Compliant Yes

Reference Finder

Item number Ampere rating Fuse size Clearing I2t At Rated Voltage Indication System Product weight
G1019251 - BTIA69V2 See product
2A A2 6.5A²s No 0.056kg
H1019252 - BTIA69V4 See product
4A A2 50A²s No 0.056kg
H1019275 - BTCP69V36 See product
36A A4 4500A²s No 0.0826kg
J1019253 - BTIA69V6 See product
6A A2 180A²s No 0.056kg
J1019276 - BTCP69V63 See product
63A A4 23000A²s No 0.0826kg
K1019254 - BTIA69V10 See product
10A A2 380A²s No 0.056kg
L1019255 - BTIA69V16 See product
16A A2 580A²s No 0.056kg
M1006606 - BTCP69V40 See product
40A A4 7400A²s No 0.0826kg
M1019256 - BTIA69V20 See product
20A A2 1450A²s No 0.056kg
N1006584 - BTIS69V36 See product
36A A3 4500A²s No 0.0578kg
Back to top